A shared non-household meter can cover tenants, cleaning, plant, catering and automatic processes with different hours. Leak detection in Uxbridge should map legitimate demand before unexplained flow is called leakage. The schedule can protect commercial confidentiality while giving the investigation a valid quiet window.

Confirm meter and users

Match the serial, units and chamber to a supplier or management record. List branches and user categories, not unnecessary individual names. Record shared or sub-meter arrangements and uncertainty.

Ofwat advises non-household customers to understand their meter and regular readings. Identity comes before logging; data from the wrong or combined meter cannot isolate a tenant’s issue.

Build an operational timeline

Record shifts, cleaning, toilets, kitchens, cooling, softeners, irrigation and other automatic events. Use start, duration and expected branch. Add exceptions such as maintenance or deliveries rather than smoothing them into an average.

Name the operational contact who can confirm a genuine no-use period. Do not shut down safety or critical equipment solely for a test without competent site approval.

Align logging and controlled tests

Verify logger clock, interval, units and installation. Mark operational events on the same timeline and record gaps. A recurring unexplained pattern supports further enquiry but does not locate the defect.

Use authorised branch isolation with affected users informed. Preserve passing valves or interrupted windows as limitations. Do not apportion cost to tenants from one technical observation.

Close after repair or explanation

Compare an equivalent operating period after repair and retain the schedule. If usage, not leakage, explains a pattern, record the process source. Keep unresolved anomalies assigned to an owner and review date.

The report should distinguish measured flow, confirmed defect and the client’s commercial decisions. This supports useful commercial leak detection without disclosing more operational detail than the technical purpose requires. Add a data-quality column for estimated events, missing tenant confirmations, clock offsets and logger gaps. The client can then decide whether another quiet window is proportionate. Store commercially sensitive schedules under restricted access and issue the repairer only the branch, timing and safety information needed for the work. Record any meter or tenant change during monitoring and split comparisons at that date rather than treating the whole period as one operating pattern.